electric generator design with Perkins engine 60KW 440V 60Hz

Basic Info

Model No.: BS-60P

Product Description

electric Generator design with Perkins Engine 60KW 440V 60Hz             Products Features

1.ISO/CE
2.1year warranty
3.spot goods,short delivery
4.diesel generator with  PERKINS  engine  

Genset Model

BS-60P

Prime Power (kw/kva)

60/75

Standby Power(kw/kva)

66/82.5

Voltage (v)

440

Rated Speed (rpm)

1800

Frequency (Hz)

60

Rated Current (A)

98.4

Connection:

3 phase 4 wire

Power Factor:

0.8

Engine Model:

1104D-E44TG1

Alternator Model:

BS224E

Net Weight (kgs)-Open

920

Net Weight (kgs)-Silent

1150

Dimensions (mm)-Open

1600X730X1200

Dimensions (mm)-Silent

2450X1000X1300

 

Engine Parameter:

Manufacturer/Model:               

Air Intake System:                              

Fuel System:         

Cylinder numbers

Displacement:

Bore x Stroke

Compression Ratio:

Max. Power:

Governing System:

PERKINS1104D-E44TG1, 4 stroke 
turbocharged, air to air charge cooled

direct injection  

4 cylinders vertical in-line

4.41L

105 x 127 mm

16.2 : 1

96.8KW / 129.8HP

Electrical

Exhaust System

Exhaust Volume:

Exhaust temperature:

Max. Allowed Back Pressure:

 17.9m³/min

 492

  15 KPa

Intake System

Max. Allowed Pressure:

Consumption:

Air Flow:

8 kPa

7.7m³/min

224.4m³/min

Fuel System

      100% Load (Prime):

75% Load(Prime):

50% Load (Prime):

224.2 g/Kw.h

237.7 g/Kw.h

257.8 g/Kw.h

Lube System

Oil Capacity:

Oil Consumption:

Engine Oil Tank Capacity:

Oil Pressure at rated speed:

8.0L

0.15% of fuel consumption

5.5 L

280 - 340 kPa

Cooling system

Coolant Capacity:

Thermostat:

Max. Water Temperature:

17with radiator / 7L without radiator

85 - 95℃

112℃

 

Alternator Parameter:        Basic Information

The alternators meet the standards of:

GB755, BS5000, VDE00530, NEMAMG1-22,IED34-1,CSA22.2 and AS1350

Technical Data:

Manufacturer:

Phases:

Connection:

Bearing numbers:

Power Factor:

Protection Class:

Altitude Condition:

Excitation:

Insulation class/Temp. rise class:

Tel. Influence Factor TIF:

Tel. Harmonic Factor THF:

Steady State Voltage Regulation:

Alternator Capacity:

Efficiency:

Cooling Air Flow:

  COPY STAMFORD,BS224E

 3

  3 phase 4 wire, Y type

  1

 0.8

 IP23

 1000M

 Brushless, self-excitation

  H / H

  <50

 <2%

 ±1%

 75KVA

 89.6%

 0.15m³/s

    Engine




Alternator   Parts for Optional       Payment Terms                         

a, T/T 30% in advance,the rest balance beford shipment.
b,L/C at sight.By 100% irrevocable L/C.                            Delivery Time           30days after receiving your advanced payment               
Warranty Policy         
Guarantee for one year or 1000 hours (accord to whichever reach first) from ex-factory 
date.During the guarantee period,our company will provide the free easy damaged 
spare part for problems caused by our quality of production or raw material except 
the damageable spare parts of diesel engine caused by customer's incorrect man  made operation.After expiration, our company provides cost parts maintenance  for gen-set.

Company Info.
Genset In Making    

Products Photo show             Genset Installation  
  Packing     Certification     Welcome to Contact me freely    

Contact us if you need more details on Electric Generator Design. We are ready to answer your questions on packaging, logistics, certification or any Other aspects about Electric Generator Design、Electric Generator Design. If these products fail to match your need, please contact us and we would like to provide relevant information.

Product Categories : Perkins Diesel Generator Set